A New Standard in Dust Collector Control Intelligence
Ecogate’s new Dust Collector Controller enhances how industrial dust collectors are controlled, monitored, and protected. Built to integrate seamlessly with the greenBOX control unit and Power Master VFDs over Modbus RTU, it brings advanced motor control, real-time diagnostics, and built-in safety logic into a single, intelligent interface. Features like automatic start/stop sequencing, condition-based monitoring, and flexible input/output options make it adaptable to a wide range of facility needs.
Announcement article to the Dust Collector Controller, click here.

Seamless Integration with the greenBOX Control Unit
The Dust Collector Controller connects directly to the greenBOX control unit over Modbus RTU, with the greenBOX acting as the Modbus Master. This connection enables real-time monitoring, remote diagnostics, and streamlined control of dust collection operations, all through the greenBOX interface.
Programming is handled using the same intuitive “listbox programming” method already used for configuring digital inputs and relay outputs on the greenBOX. Firmware updates for the Dust Collector Controller are delivered automatically via Modbus, ensuring the system stays current without requiring additional software.
Note: While sawdust is used as a typical example, the principles described apply broadly across most types of industrial nuisance dust.
Real-Time Sensor Data and Safety Monitoring
The Dust Collector Controller aggregates data from critical sensors including fan total static pressure, filter differential pressure, and air velocity/volume (via the Ecogate Averaging Air Velocity Sensor). All of this data is transmitted over Modbus to the greenBOX for live monitoring and control.
Additional sensors and safety devices can be connected directly to the Dust Collector Interface via programmable digital inputs or 4–20 mA analog inputs. An air quality sensor can also be connected to the Dust Collector Controller via Modbus, serving dual purposes: detecting broken filter bags and triggering automatic antifreeze mode in cold conditions.
This architecture gives you a complete, real-time view of dust collection system performance and safety, helping to prevent issues before they escalate.
Power Master VFD Integration and Remote Control Capabilities
The Dust Collector Controller connects directly to the Power Master VFD, enabling remote start/stop functionality even if the greenBOX is offline. This ensures key safety features remain active regardless of how the fan is operated.
The Dust Collector interface provides an Enable signal to the VFD:
Closed contact: All dust collector components are operating normally — safe to run the fan.
Open contact: A fault has been detected — the fan should shut down to prevent damage or overfill.
For example, if an airlock motor fails and goes unnoticed, the dust collector can quickly fill with material, leading to costly downtime. The Dust Collector Controller proactively prevents such scenarios.
Full Control of All Dust Collector Motors by VFD
The Dust Collector Controller can control all dust collector motors — including the airlock, rotating cleaning arm, cleaning pump, and transport fan — via VFDs for each component. A second Modbus terminal on the controller enables it to act as a Modbus Master, communicating directly with each VFD as a Slave.
This architecture provides:
Smooth motor startup and shutdown, reducing peak current draw and mechanical stress
Live readouts of motor voltage, current, power, and speed, available locally and remotely
Condition-based diagnostics, allowing early detection of issues like locked motors, broken belts, or stalled drives
VFDs today offer greater long-term reliability than electromechanical contactors — a shift backed by Mean Time Between Failure (MTBF) data. In fact, Ecogate’s own field experience with Yaskawa P7 Bypass VFDs showed that contactors — originally intended as backup — failed more often than the VFDs themselves. This insight helped drive our decision to design full VFD integration into the Dust Collector Controller.

Intelligent Start and Stop Sequences
The Ecogate system operates on demand. The Dust Collector Controller works in coordination with the greenBOX to automate how and when the dust collector starts and stops, based entirely on production activity.
Each workstation is equipped with a sensor that signals the greenBOX when dust extraction is needed. This triggers both the main fan and the dust collector to start. When all workstations are idle, the system initiates an automatic shutdown: the fan stops first, followed by a delayed stop of the internal dust collector components.
This sequence eliminates manual startup and shutdown before and after shifts. It reduces energy consumption, avoids unnecessary runtime, and minimizes mechanical wear on the system.
Start Sequence
To reduce electrical peak demand, motors are started in a specific order. The sequence begins with the component located farthest downstream:
Transport fan
Airlock
Cleaning arm
Cleaning pump (if equipped)
A three-second delay between each motor startup helps smooth power usage and prevent inrush current spikes.
Stop Sequence
Once the main fan shuts off, the controller applies a delayed shutdown to the internal motors. This allows any remaining material to clear out of the dust collector, reducing the risk of jams or blockages during the next cycle.
Depending on system size, the cleanout delay is typically set between five and ten minutes.
Built-In Safety Logic to Protect People and Property
Dust collection systems can pose significant safety risks if not properly monitored. The Dust Collector Controller includes built-in logic to respond to unsafe conditions in real time, protecting personnel, equipment, and the facility.
Key safety systems supported include:
Factory Fire Alarm – Automatically shuts down the system to prevent fire spread.
Spark Detection System – If a spark is detected and not extinguished, the controller triggers the abort gate and shuts down the system.
Airlock and Cleaning Arm Monitoring – Zero-speed detection halts the system if a motor fails to rotate.
Transport System Monitoring – Ensures containers or silos aren’t full and all transport components are functioning correctly.
These safeguards are designed to catch issues early and shut down only when necessary.
Customizable for Any Facility
Every facility is different, and the Dust Collector Controller can be configured to match your exact operational needs. Through programmable logic and flexible input/output options, the system supports:
Automatic container switching using diverting gates
Coordinated control across multiple dust collectors sharing a common transport system
Cold-weather antifreeze logic to protect components in low temperatures
Custom safety or sequencing logic tailored to plant-specific requirements
Whether you’re managing a single collector or a complex multi-unit system, the controller adapts to your layout and priorities without requiring custom software or PLC programming.
Conclusion
Ecogate’s Dust Collector Controller brings a new level of intelligence, visibility, and protection to industrial dust collectors. With seamless integration into the Ecogate system, full motor control via VFDs, and built-in safety logic, it simplifies system management while enhancing operational safety and efficiency.
From automated sequencing to real-time diagnostics, the controller reduces manual overhead and helps prevent costly downtime. Its flexible architecture supports a wide range of configurations making it an ideal fit for both standard and complex facility layouts.
Whether you're upgrading a single collector or scaling up a plant-wide system, the Dust Collector Controller gives you the tools to run smarter, safer, and more efficiently.
Smarter Dust Collector Control Starts Here
Looking to improve safety, reduce energy costs, or simplify dust collection management?Ecogate’s Dust Collector Controller delivers intelligent automation, full visibility, and seamless integration — all through one interface.